20
Performance Specifications
Section 2-1
2-1
Performance Specifications
2-1-1
Available Models
Note
Supported only by lot numbers of 0209__ or higher.
2-1-2
Specifications
Model number
Program
capacity
I/O points (built-in)
Special I/O
Built-in
peripheral
port
Contact
input
Contact
output
Pulse input (high-
speed counters)
Pulse
outputs
Analog
outputs
Analog
inputs
Compatible
with servo
driver with
absolute
encoder
(See note)
CS1W-HIO01-V1 4 Kwords
12 inputs
(24 VDC)
(4 inputs
can be
used as
interrupt
inputs)
8 transistor
outputs
(sinking)
None
No
None
None
None
For Pro-
gramming
Console or
CX-Pro-
grammer
CS1W-HCP22-
V1
2 pts
Yes
2 pts
None
None
CS1W-HCA22-
V1
2 pts
Yes
None
2 pts
None
CS1W-HCA12-
V1
1 pts
Yes
None
2 pts
1 pts
Item
Specification
Model number
CS1W-HIO01-V1/CS1W-HCP22-V1/CS1W-HCA22-V1/CS1W-
HCA12-V1
Unit classification
CS1 Special I/O Unit
Applicable PLCs
CS-series PLCs
Applicable unit numbers
00 to 95 (Must not be duplicated with other Special I/O Units)
Applicable Rack/slot
CS-series CPU Rack or Expansion Rack
Note
1.
There are no restrictions on the mounting slot.
2.
Mounting to C200H Expansion Racks or SYSMAC
BUS Slave Racks is not possible.
Exchange of
specific data
with CPU Unit
Special I/O Unit Area
(CIO n to n+9;
n = 2000 + (unit number
´
10))
10 words per Unit (data exchanged constantly)
5 words: CPU Unit
®
Customizable Counter Unit (RUN/STOP com-
mands, general-purpose output data)
5 words: Customizable Counter Unit
®
CPU Unit (Unit status, gen-
eral-purpose input data)
DM Area words allocated to Spe-
cial I/O Units (m to m+99;
m = (unit number
´
99))
100 words per Unit
Initial settings
from the CPU
Unit
10 words: System Setup Area (transferred from the CPU Unit to the
Customizable Counter Unit at startup or Unit restart).
The System Setup Area contains the following settings: Enable/dis-
able of RUN/STOP command from the CPU Unit; startup operating
mode; specification of beginning word addresses for the output and
input areas for data exchange with the CPU Unit; number of
exchange words; the area used as the data exchange area in the
Customizable Counter Unit; address specifications, etc.
Area for
exchanging
general-pur-
pose data with
the CPU Unit
90 words: For exchanging the general-purpose data listed below.
Содержание CS1W-HCA12-V1
Страница 2: ......
Страница 6: ...vi...
Страница 20: ...xx Conformance to EC Directives 7...
Страница 38: ...18 Models and System Configurations Section 1 2...
Страница 78: ...58 Fail safe Circuits Section 3 5...
Страница 138: ...118 AR Area Section 6 4...
Страница 204: ...184 Improved Instructions Section 7 14...
Страница 222: ...202 Cycle Time Section 8 3...
Страница 240: ...220 Troubleshooting Flowcharts Section 9 5...
Страница 244: ...224 Precautions when Using the CX Programmer Appendix A...
Страница 252: ......
Страница 253: ......