44
SE
C
T
IO
N
2
Co
nnec
tions
and Wir
in
g
RFID System
User's Manual
SECTION 2
CS-series ID Sensor Units
• Noise Countermeasures for External Wiring
Consider the following items when wiring external lines, such as Antenna cable, I/O lines, power supply
lines, and high-power lines.
• When using multiconductor cables for signal lines, do not use the same cable for both I/O lines and
other control lines.
• When Racks are installed in parallel with each other, keep them separated by at least 300 mm.
• When placing cables in the same duct, separate them with grounded iron plates.
300 mm min.
300 mm min.
Ground to 100
Ω
or less.
Low-power cables
Control cables
High-power cables
Antenna cables
and PLC I/O lines
SYSMAC power supply
lines and general
control circuit lines
Power lines
200 mm min.
Ground to 100
Ω
or less.
Power lines
PLC I/O lines
SYSMAC power supply
lines and general
control circuit lines
Iron plate