• Noise Countermeasures for External Wiring
Consider the following items when wiring external lines, such as the Antenna cable, I/O lines, power
supply lines, and high-power lines.
• When using multiconductor cables for signal lines, do not use the same cable for both I/O lines and
other control lines.
• When Racks are installed in parallel with each other, keep them separated by at least 300 mm.
• When placing cables in the same duct, separate them with grounded iron plates.
300 mm min.
300 mm min.
Power lines
Low-power cables
Control cables
High-power cables
Antenna cables and
PLC I/O lines
Ground to 100
Ω
or less.
SYSMAC power supply
lines and general
control circuit lines
200 mm min.
Power lines
PLC I/O lines
Ground to 100
Ω
or less.
Iron plate
SYSMAC power supply
lines and general
control circuit lines