CP CU1
CP CU1 - 1
The
CP CU1
’s outputs and the connected cables carry life-hazardous voltage or current.
►
Always obey the five safety rules and follow the detailed safety instructions below.
Note:
The safety instructions relevant to the
CPC 100
and its accessories (refer to page
Preface-1) also apply to the
CP CU1
. This section lists safety instructions that exclusively apply
to the
CP CU1
.
General
►
Before operating the
CP CU1
, read the CP CU1 Reference Manual carefully and observe
the safety rules and instructions therein.
►
Before handling the
CP CU1
or
CPC 100
in any way, connect them with a solid connection
of at least 6 mm² cross-section to ground. Ground the
CP CU1
as close as possible to the
CPC 100
.
►
Use the
CP GB1
grounding box to connect the
CP CU1
to overhead lines and power cables.
For detailed information, see the application-specific “Safety Instructions for Connecting
CP CU1
to Power Lines” in the CP CU1 Reference Manual.
►
When using the
CP GB1
, ground it near the place where the connection to the test object is
made. Make sure that the grounding stud is in good condition, clean and free of oxidation.
►
Make sure that all studs and cables of the
CP GB1
are screwed tight.
►
Make sure that the test object’s terminals to be connected to the
CP CU1
do not carry any
voltage potential. During a test, the only power source for a test object may be the
CP CU1
(powered by the
CPC 100
). The only exception are measurements on overhead lines as
described in “Applications” in the CP CU1 Reference Manual.
►
Use the
CP CU1
,
CP GB1
and their accessories only in a technically sound condition and
when its use is in accordance with the regulations. In particular, avoid disruptions that could
in turn affect safety.
Operating the Measurement Setup
►
When using the
CP GB1
, ground it near the place where the connection to the test object is
made. Make sure that the grounding stud is in good condition, clean and free of oxidation.
►
Life threatening voltages up to 600 V can appear on all
CP GB1
contacts and on all clamps
and cables connected to the
CP CU1
during the test. Keep safe distance from them.
►
Before handling the
CP CU1
or
CP GB1
in any way (even before setting the current range
switch), make sure that the device under test (e.g. overhead lines or power cables) are well
grounded (e.g. by closing the grounding switch) near the measurement setup.
►
Ensure that the short-circuit bar is always plugged in the
CP CU1
I AC
output whenever the
output is not connected to the
I AC
input of the
CPC 100
.
►
Connect the
CP CU1
I AC
output exclusively to the
I AC
input of the
CPC 100
.
►
Before connecting the
CP CU1
with the
CPC 100
, turn off the
CPC 100
either by the
POWER ON/OFF switch or the Emergency Stop button.
►
Set the current range switch on the
CP CU1
front panel only when the
CPC 100
is turned
off and the test object is grounded.
►
In addition to the above safety rules follow the application-specific “Safety Instructions for
Connecting
CP CU1
to Power Lines” in the CP CU1 Reference Manual.
►
The
CP CU1
may be used only as described in “Applications” in the CP CU1 Reference
Manual. Any other use is not in accordance with the regulations. The manufacturer and/or
distributor is not liable for damage resulting from improper usage. The user alone assumes
all responsibility and risk.
BOOSTER
Surge arrestor
VT
V1 AC (0 … 30 V)
Voltmeter
V SENSE (0 … 600 V)
I OUT (0 … 100 A)
CT
Fuse 30 A
Power transformer
Current range switch
Surge arrestor
I AC (0 … 2.5 A)
Safety Instructions
Block Diagram
CP CU1
Содержание CPC 100
Страница 13: ...CPC 100 V 3 20 Introduction 8 Introduction...
Страница 25: ...CPC 100 V 3 20 Current Transformer 10 Current Transformer...
Страница 29: ...CPC 100 V 3 20 Voltage Transformer 4 Voltage Transformer...
Страница 65: ...CP TD1 CP TD1 10 CP TD1...
Страница 75: ...CP SB1 CP SB1 4 CP SB1...