CP CU1
CP CU1 - 2
CP CU1
The
CP GB1
grounding box is a surge arrestor unit for connecting the
CP CU1
to the test object.
If high voltage appears for a short time on the test object’s terminals, an arc discharges the
voltage and extinguishes without destroying the grounding box. If the arc persists for a longer
time period, the surge arrestor insulator melts and the terminals are short-circuited to ground,
thereby protecting the operating staff,
CP CU1
and
CPC 100
.
To short the phases, connect the line studs of the
CP GB1
as shown below.
DANGER
Death or severe injury caused by high voltage or current
►
Use the short-circuit bar to short-circuit the secondary side of the internal CT.
Equipotential ground
terminal
I AC output
Location to store the
short-circuit bar
V1 AC output
VT 600 V : 30 V
V SENSE input
Fuse 30 A
BOOSTER input
Voltmeter
Current range switch
CT 100 A : 2.5 A
I OUT output
To test object
To
CP CU1
Surge arrestor
Ground connection
DANGER
Death or severe injury caused by high voltage or current
►
The
CP GB1
grounding box must be used for measurements on overhead lines or
power cables.
►
Check the surge arrestors before using the
CP GB1
. Refer to the CP CU1
Reference Manual for more Information.
Functional Elements
CP GB1
Grounding Box