CPC 100 Technical Data - 3
Additional Features of the Measuring Inputs
•
Automatic range switching (except test card
Amplifier
)
•
Galvanically separated potential groups:
I AC / DC
;
V1
&
V2
;
V DC
•
AC frequency range 15 … 400 Hz (except test card
Amplifier
)
•
Protection of
I AC / DC
input: 10A FF fuse
4
Binary input for dry contacts or voltages up to 300V DC
7
The accuracy of the resistance measurements can be calculated from the respective input and
output specifications.
Trigger criteria
Toggling with potential-free contacts or voltages of up to 300 V
Input impedance
> 100 k
Response time
1 ms
4-wire measurement with 400A DC output and 10V VDC input
Current
Resistance
Voltage
Typ. error
Guaranteed
400 A
10
4 mV
0.70 %
1.35 %
400 A
100
40 mV
0.55 %
1.10 %
400 A
1 m
400 mV
0.50 %
0.95 %
400 A
10 m
4 V
0.50 %
0.95 %
4-wire measurement with 6A DC output and 10V VDC input
Current
Resistance
Voltage
Typ. error
Guaranteed
6 A
100 m
0.6 V
0.35 %
0.60 %
6 A
1
6 V
0.35 %
0.60 %
1 A
10
10 V
0.25 %
0.40 %
2-wire measurement with 10V VDC input
Current
Resistance
Voltage
Typ. error
Guaranteed
< 5 mA
100
0.60 %
1.20 %
< 5 mA
1 k
0.51 %
1.02 %
< 5 mA
10 k
0.50 %
1.00 %
Display
¼ VGA greyscale LCD display
Power supply
Single-phase, nominal
9
100V AC … 240V AC, 16A
Single-phase, permissible
85V AC … 264V AC (L-N or L-L)
Frequency, nominal
50/60 Hz
Power consumption
< 7000 VA for a time < 10 s
Connection
IEC320/C20
Environmental conditions
Operating temperature
-10 ° … +55 °C (+14 … +131 F)
Storage temperature
-20 ° … +70 °C (-4 … +158 F)
Humidity range
5 … 95 % relative humidity, no condensation
Shock
IEC68-2-27 (operating), 15 g/11 ms, half-sinusoid
Vibration
IEC68-2-6 (operating), 10 … 150 Hz, acceleration 2 g
continuous (20 m/s²); 10 cycles per axis
EMC
EN 50081-2, EN 55011, EN 61000-3-2, FCC Subpart B of Part
15 Class A, EN 50082-2, IEC 61000-4-2/3/4/8, CE conform
(89/336/EEC)
Safety
EN 61010-1, EN 60950, IEC 61010-1, produced and tested in
an EN ISO 9001 certified company.
Prepared for
IEEE 510, EN 50191, VDE 104
Measuring Inputs
Resistance Measurement
General
Содержание CPC 100
Страница 13: ...CPC 100 V 3 20 Introduction 8 Introduction...
Страница 25: ...CPC 100 V 3 20 Current Transformer 10 Current Transformer...
Страница 29: ...CPC 100 V 3 20 Voltage Transformer 4 Voltage Transformer...
Страница 65: ...CP TD1 CP TD1 10 CP TD1...
Страница 75: ...CP SB1 CP SB1 4 CP SB1...