CP TD1
CP TD1 - 6
CP TD1
Pressing the
Settings
button on the
TanDelta
main page opens the
Settings
page allowing you
to set additional measurement options.
Filter bandwidth of measurement.
Note:
If the test frequency equals the default frequency (as set at
Options
|
Device Setup
),
the filter bandwidth is always ± 5 Hz, regardless of the set value. This even applies if the option
"use default frequency of xx.xx Hz" is not specifically selected.
± 5 Hz means that interferences at frequencies with an offset of
± 5 Hz from the measuring
frequency will not affect the results.
The smaller the filter bandwidth, the longer the measuring time.
The averaging factor determines the
number of measurements. A factor of 3
means: the
CP TD1
carries out 3
measurements whose results are then
averaged. The higher the factor, the
more accurate the measurement but
the longer the measuring time.
Compound measurement setting
Cp, DF (tan
) = parallel capacitance & dissipation factor
Cp, PF (cos
) = parallel capacitance & power factor
Cp, Ptest = parallel capacitance & power
Cp, P@10kV = parallel capacitance & power; linearly interpolated to 10 kV test voltage
Qtest, Stest = reactive & apparent power
Z = impedance with phase angle
Cp, Rp = parallel capacitance & parallel resistance
Ls, Rs = serial inductance & serial resistance
Cp, QF = parallel capacitance & quality factor
Ls, QF = series inductance & quality factor
If selected, the
CPC 100
checks whether the shield of the high-voltage cable is connected. For
some large inductive loads, the
CPC 100
can accidentally report shield check error even when
the shield is connected. If this is the case, it makes sense to clear the check box.
If selected, the beeper sounds during
the entire test. If cleared, the beeper
sounds at the beginning and the end of
the test only.
At "Assessment Limits", set the tolerance of the
main page’s nominal values for the assessment.
For the capacitance, the tolerance is entered in
percent, for the dissipation factor it’s a multiplier.
Note:
Availability and naming of the entry fields
depend on the measuring mode, e.g., DF and PF
are the same entry field.
The
CP TD1
leaves OMICRON
electronics factory-calibrated. If a
component needs to be exchanged by a
spare part, the
CP TD1
must be re-
calibrated.
To re-calibrate, set the focus onto the
test card tab designation
TanDelta
and
press
Edit Calib
to enable the entry
fields:
•
Cx = correction factor for Cmeas
(multiplier)
•
DF/PF + = corrective value added
to dissipation or power factor (can
be + or -)
Note:
Enter your name and press
Update Calib
to complete the re-
calibration.
See also figure
CP TD1
CP CAL1
on
page CP TD1-3.
Select if you use an external CT.
The entered ratio is used to calculate
the measured current accordingly.
Note:
"Use ext. CT" can only be
selected if there are no measurement
results yet.
Returns to
TanDelta
’s main page
Selecting “Compensations" converts the actually measured dissipation or power factor to
normalized values corresponding to an ambient temperature of 20 °C. In doing so, the values
entered at "Compensations" represent the existing ambient condition.
►
Enter oil temperature, ambient temperature (at bushing) and relative humidity first.
►
Then place the cursor on "k".
The medium the measurement takes place in, oil or air, determines the k-factor.
•
ANSI C57.12
The oil temperature is the determining medium for the k-factor.
•
Bushings
The air temperature at the respective bushing is the determining medium for the k-factor.
Bushings
provides three bushing types to select from: RBP (
R
esin
B
onded
P
aper), RIP
(
R
esin
I
mpregnated
P
aper) and OIP (
O
il
I
mpregnated
P
aper). The k-factor changes
accordingly.
TanDelta-PF Test Card - Main Page
TanDelta-PF Test Card - Settings Page
Содержание CPC 100
Страница 13: ...CPC 100 V 3 20 Introduction 8 Introduction...
Страница 25: ...CPC 100 V 3 20 Current Transformer 10 Current Transformer...
Страница 29: ...CPC 100 V 3 20 Voltage Transformer 4 Voltage Transformer...
Страница 65: ...CP TD1 CP TD1 10 CP TD1...
Страница 75: ...CP SB1 CP SB1 4 CP SB1...