CPC 100
V 3.20
Transformer - 5
Use the
RWinding
test card to measure the resistance of a power transformer’s winding as
described on page Current Transformer-4. Alternatively, inject the current directly from the
400A DC
output as shown below.
The
Tap Changer Cleaner Sequence
is used to sweep all taps before performing a
Winding
Resistance
measurement to ensure that the taps are clean.
Note:
The
Tap Changer Cleaner Sequence
can only be activated if the
CP SB1
transformer
switch box is connected and
Auto-tap
is selected.
The currently sweeped tap and the remaining time are displayed during the sequence.
Note:
You can only interrupt the
Tap Changer Cleaner Sequence
by pressing the Emergency
Stop button.
CP SB1
transformer
switch box
DANGER
Death or severe injury caused by high voltage or current
►
Connect the
CP SA1
discharge box to the
CPC 100
's
V DC
input sockets.
CP SA1
NOTICE
The
CP SA1
discharge
box also protects the
CPC 100
from damages
caused by high voltage.
1 sweep = every tap
position is actuated
once in each
direction
Measurement
temperature
Time required for
switching between
two taps
Reference
temperature
Click to start
Cleaner
Sequence
Vector Group Check
Winding Resistance
Tap Changer Cleaner Sequence