CP CU1
CP CU1 - 6
CP CU1
There are four measurements with different connections. For detailed information, refer to the
template or the CP CU1 Reference Manual.
For step and touch voltage measurements using the
HGT1
FFT voltmeter, refer to the
HGT1 User Manual.
Output Ranges
Accuracy
I AC
BOOSTER
I OUT
CP CU1
V2 AC
I AC
CPC 100
EXT. BOOSTER
CP GB1
Signal cable
I AC
CPC 100
EXT. BOOSTER
I AC
BOOSTER
I OUT
CP CU1
CP GB1
Fence
Range
Current
Compliance Voltage @ > 45 Hz
10 A
0 … 10 Arms
500 Vrms
5000 VA (45 … 70 Hz)
cos
< 1.0 @ 230 V AC mains voltage
cos
< 0.4 @ 115 V AC mains voltage
for 8 s or 1600 VA continuously
20 A
0 … 20 Arms
250 Vrms
50 A
0 … 50 Arms
100 Vrms
100 A
0 … 100 Arms
50 Vrms
Impedance
Range
Typical
Accuracy of
abs(Z)
Typical
Accuracy of
Phase
V SENSE
Voltage
I OUT
Current
Current
Range
0.05 … 0.2
1.0 … 0.5 %
1.5 … 0.8°
5 … 20 V
100 A
100 A
0.2 … 2
0.5 … 0.3 %
0.8 … 0.5°
20 … 50 V
100 … 25 A
100 A
2 … 5
0.3 %
0.5°
100 V
50 … 20 A
50 A
5 … 25
0.3 %
0.5°
100 … 250 V
20 … 10 A
20 A
25 … 300
0.3 … 1.0 %
0.5 … 1.5°
250 … 500 V
10 … 1.5 A
10 A
Measurement of Coupling into Signal Cables
Step and Touch Voltage Measurement
Technical Data