CP CB2
CP CB2 - 2
CP CB2
Weight and Dimensions
Notes regarding the
CP CB2
1. With a mains voltage of 230 V using a 2 x 0.6 m high-current cable at an ambient
temperature of 23 °C ± 5 ° (73 °F ± 10 °F)
2. Signals below 50 Hz or above 60 Hz with reduced values possible
Note:
Make sure to establish series or parallel connection, depending on the selected range on
the test card.
Current outputs
Range
Amplitude
t
max
1
V
max
2
Power
max
2
f
1000 A AC
0 … 1000 A
25 s
4.90 V
4900 VA
15 … 400 Hz
0 … 500 A
30 min
5.00 V
2500 VA
15 … 400 Hz
2000 A AC
0 … 2000 A
25 s
2.45 V
4900 VA
15 … 400 Hz
Internal measurement of outputs
Output
Guaranteed accuracy
Typical accuracy
Amplitude
Phase
Amplitude
Phase
Reading
error
Full
scale
error
Full
scale
error
Reading
error
Full
scale
error
Full
scale
error
2000 A AC
0.25 %
0.25 %
0.50°
0.13 %
0.13 %
0.25°
1000 A AC
0.25 %
0.25 %
0.50°
0.13 %
0.13 %
0.25°
Weight
Dimensions (W x H x D)
CP CB2
test set
16 kg (35.3 lbs)
186 x 166 x 220 mm (7.3 x 6.5 x 8.7”),
without handle.
test set & case
25 kg (55.1 lbs)
700 x 450 x 360 mm (27.6 x 17.7 x
14.2”)
DANGER
Death or severe injury caused by high voltage or current
►
Do not touch the
CPC 100
’s outputs and do not touch or unplug any cables while
working with the
CP CB2
.
Technical Data