CPC 100
V 3.20
Current Transformer - 2
Current
Transformer
Additional measurements when
Measure Burden
is selected:
Note:
For the meaning of the other test card components, refer to page Current Transformer-1.
This is the preferred method in cases, when the current of max. 800 A that the
CPC 100
can
feed into the CT’s primary side is not sufficient.
V sec: measured secondary voltage and
phase angle relative to Iprim
Burden in VA: I sec nom × (V sec act ×
I sec nom/I sec act)
cos
: cosine of angle between I sec and V sec
B
u
rden
CT
Select to enter
secondary voltage
instead of
measuring it
Select to stop test automatically when
measurement is done.
Nominal secondary
current
Output frequency
Secondary
injection current
from
6A AC
output
Actual injection
current measured
via input
I AC
Secondary
voltage at the
burden,
measured at input
V1 AC
, and
phase angle
relative to Isec
Burden in VA: I sec nom ×
(V sec act × I sec nom/I sec act)
Cosinus of phase
angle
CTRatio (with Burden) - The Option Measure Burden
CTBurden