CPC 100
V 3.20
Voltage Transformer - 3
Use the
VTElectronics
test card to test the ratio of non-conventional electronic voltage
transformers with a very low-level secondary voltage.
Shielded cable with
twisted wires
Electronic protection relay with
low-voltage input
Electronic voltage transformer
Nominal primary voltage
Primary
injection
voltage
Correction factor for
V prim
Measured
primary voltage
Secondary
voltage measured
at
V1 AC
, and its
phase angle
relative to the
measured Vprim
Nominal secondary voltage
Select to stop test
automatically when
measurement is
done
Output
frequency
1/
3 and 1/3: Correction factors for V sec
Select to enter
secondary voltage
instead of
measuring it
Ratio and deviation in %
Polarity:
OK
= phase I sec - phase I prim
= - 45 ° < 0 ° < + 45 °
NOTOK
= all other cases
VTElectronics