4 Commissioning
BU 0180 en-4118
79
4.4 Temperature sensors
The current vector control of the frequency inverter can be further optimised by the use of a
temperature sensor
. By continuous measurement of the motor temperature, the highest precision of
regulation by the frequency inverter and the associated optimum speed precision of the motor is
achieved at all times. As the temperature measurement starts immediately after the (mains) switch-on
of the frequency inverter, the frequency inverter provides immediate optimum control, even if the
motor has a considerably increased temperature after an intermediate "Mains off / Mains on" of the
frequency inverter.
Information
To determine the stator resistance of the motor, the temperature range 15 … 25 °C should not be exceeded.
Excess temperature of the motor is also monitored and at 155 °C (switching threshold for the thermistor) causes
the drive unit to shut down with error message E002.
Information
Pay attention to polarity
Temperature sensors are wired semiconductors that must be operated in the conducting direction. In order to do
this, the anode must be connected to the "+" contact of the analogue input. The cathode must be connected to
the "-" ground or ground contact of the analogue input.
Failure to observe this can lead to false measurements. Motor winding protection is therefore no longer
guaranteed.
Approved temperature sensors
The function of approved temperature sensors is comparable. However, their characteristic curves
differ. Correct matching of the characteristic curves to the frequency inverter is made by changing the
following two parameters.
Sensor type
Shunt resistor
P402[xx]
1)
0 % Adjustment
P403[xx]
1)
100 % Adjustment
[kΩ]
[V]
[V]
KTY84-130
2.7
1.54
2.64
PT100
2.7
0.36
0.49
PT1000
2.7
2.68
3.32
1)
Xx = Parameter array, depending on the analog input used
Table 10: Temperature sensors, adjustment
Connection of a temperature sensor is made according to the following examples.
Taking into account the relevant values for the 0% adjustment [P402] and 100% adjustment [P403],
these examples can be used for all of the approved temperature sensors which are stated above.
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...