NORDAC BASE (SK 180E / SK 190E) – Users Manual for Frequency Inverters
138
BU 0180 en-4118
P520
Flying start
(Flying start)
S
P
0 ... 4
{ 0 }
This function is required to connect the FI to already rotating motors, e.g. in fan drives. Motor
frequencies >100Hz are only picked up in speed controlled mode (Servo mode P300 = ON).
0 = Switched off
, no flying start.
1 = Both directions
, the FI looks for a speed in both directions.
2 = Setpoint value direction
, searches only in the direction of the setpoint val. which is present.
3 = Both directions after failure
, as for { 1 }, however only after mains failure or fault
4 = Setpoint direction after fail
, as for{ 2 }, however only after mains failure or fault
NOTE:
For physical reasons, the flying start circuit only operates above 1/10 of the nominal
motor frequency (P201), however, not below 10Hz.
Example 1
Example 2
(P201)
50Hz
200Hz
f=1/10*(P201)
f=5Hz
f=20Hz
Comparison of f with
f
min
with:
f
min
=10Hz
Result f
Fang
=
5Hz < 10Hz
The flying start circuit
functions above
f
Fang
=10Hz.
20Hz < 10Hz
The flying start circuit
functions above
f
Fang
=20Hz.
P521
Fly. start resol.
(Flying start resolution)
S
P
0.02... 2.50 Hz
{ 0.05 }
Using this parameter, the flying start circuit search increment size can be adjusted. Values that
are too large affect accuracy and causes the FI to cut out with an overcurrent message. If the
values are too small, the search time is greatly extended.
P522
Fly. start offset
(Flying start offset)
S
P
-10.0 ... 10.0 Hz
{ 0.0 }
A frequency value that can be added to the frequency value found, e.g. to remain in the motor
range and so avoid the generator range and therefore the chopper range.
P523
Factory setting
(Factory setting)
0 ... 3
{ 0 }
By selecting the appropriate value and confirming it with the Enter key, the selected parameter
range is entered in the factory setting. Once the setting has been made, the value of the
parameter returns automatically to 0.
0 = No change:
Does not change the parameterisation.
1 = Load factory settings:
The complete parameterisation of the FI reverts to the factory
setting. All originally parameterised data are lost.
2 = Factory settings without bus:
All parameters of the frequency inverter, with the
exception of the bus parameter, are reset to the factory setting.
3 = Factory settings without motor data:
All parameters of the frequency inverter, but not
the motor data parameters (P2xx), are reset to the factory setting.
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...