5 Parameter
BU 0180 en-4118
127
P428
Automatic start
(
Automatic start)
S
P
0 ... 1
{ 0 }
In the standard setting (P428 =
0
Off
) the inverter requires a flank to enable (signal change
from "low
high") at the relevant digital input.
In the setting
On
1
the FI reacts to a High level. This function is only possible if the FI is
controlled using the digital inputs. (see P509=0/1)
In certain cases, the FI must start up directly when the mains are switched on. For this P428 =
1
On
can be set. If the enable signal is permanently switched on, or equipped with a cable
jumper, the FI starts up immediately.
NOTE:
(P428) not "ON" if (P506) = 6,
Danger!
(See note on (P506))
NOTE:
The "Automatic Start" function can only be used if a digital input of the frequency
inverter (DIN 1 …) is parameterised to the function "Enable Right" or "Enable Left"
and this input is permanently set to "High". The digital inputs of the technology
modules (e.g.: SK CU4 - IOE) do not support this "Automatic Start" function!
NOTE:
The "Automatic Start" function can only be activated if the frequency inverter has
been parameterised to local control ((P509) setting { 0 } or { 1} ).
P434
[-01]
[-02]
Digital output function
(Digital output function)
0 ... 40
{ 7 }
[-01] =
Digital output 1,
Digital output 1 of the frequency inverter
[-02] =
Digital output 2,
Digital output 2 of the frequency inverter
Settings 3 to 5 and 11 work with a 10% hysteresis, i.e. the output delivers (function 11 does not deliver)
when the 24V limit value is reached and switches off again when the value drops to a value that is 10
% less again (function 11 on again).
This behaviour can be inverted with a negative value in P435.
Setting / Function
Output ...
with limit value
or function
(see also P435)
0 = No function
Low
1 = External brake
, to control an external 24V brake relay (max. 20 mA). The
output switches at a programmed absolute minimum frequency (P505).
For typical brakes a setpoint delay of 0.2-0.3s should be programmed (see
also P107/P114).
Low
2 = Inverter operating
, the output indicates voltage at the FI output (U - V - W).
High
3 = Current limit
, based on the setting of the motor rated current (P203). This
value can be adjusted via the standardisation (P435).
High
4 = Torque current limit
, based on motor data settings in P203 and P206.
Signals a corresponding torque load on the motor. This value can be adjusted
with the standardisation (P435).
High
5 = Frequency limit
, based on motor nominal frequency setting in P201. This
value can be adjusted via the standardisation (P435).
High
6 = Setpoint reached
, indicates that the FI has completed the frequency increase
or decrease. Setpoint frequency = actual frequency! From a difference of 1 Hz
Setpoint value not achieved
–
signal Low.
High
7 = Error,
general error message, error is active or not yet acknowledged.
Fault
-
Low (Ready
-
High)
Low
8 = Warning:
general warning, a limit value was reached that could lead to a later
shutdown of the FI.
Low
9 = Overcurrent warning
: At least 130 % of the nominal FI current was supplied
for 30 s.
Low
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...