4 Commissioning
BU 0180 en-4118
83
– or via M12 flange connector
Technical data for AS interface
Designation
Value
AS-i supply, PWR connection (yellow cable)
24 V DC, max. 25 mA
Slave profile
S-7.A
I/O-Code
7
ID Code
A
External ID Code 1 / 2
7
Address
1A – 31A and 1B - 31B
(Delivery condition 0A)
Cycle time
Slave
Master ≤
10 ms
Master
Slave ≤
21 ms
Quantity of (BUS I/O)
4I / 4O
4.5.3 Bus structure and topology
The AS Interface network must be set up in any form (line, star, ring and tree structure) and is
managed by an AS interface master as the interface between the PLC and slaves. Additional slaves
can be added to an existing network at any time, up to a limit of 31 standard slaves or 62 A/B slaves.
The slaves are addressed by the master or an appropriate addressing device.
An AS-i master communicates independently and exchanges data with the connected AS-i slaves.
Normal power units may not be used in the AS interface network. Only a special AS interface power
unit may be used for the power supply for each AS interface connector. This AS interface power
supply is directly connected to the yellow standard cable (AS-i(+) and AS-i(-) cable) and should be
positioned as close as possible to the AS-i master in order to keep the voltage drop small.
In order to avoid problems, the
PE connection of the AS interface power supply
(if present)
must
be earthed
.
The brown
AS-i(+)
and the blue
AS-i(-)
wire of the yellow AS interface cable
must not be earthed
.
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...