8 Additional information
BU 0180 en-4118
187
8.4.2 Reduced overcurrent due to time
The possible overload capacity changes depending on the duration of an overload. Several values are
cited in this table. If one of these limiting values is reached, the frequency inverter must have sufficient
time (with low utilisation or without load) in order to regenerate itself.
If operated repeatedly in the overload region at short intervals, the limiting values stated in the tables
are reduced.
230V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency
[kHz]
Time [s]
> 600
60
30
20
10
3.5
3...8
110%
150%
170%
180%
180%
200%
10
103%
140%
155%
165%
165%
180%
12
96%
130%
145%
155%
155%
160%
14
90%
120%
135%
145%
145%
150%
16
82%
110%
125%
135%
135%
140%
400V devices:
Reduced overload capacity (approx.) due to pulse frequency (P504) and time
Pulse frequency
[kHz]
Time [s]
> 600
60
30
20
10
3.5
3...6
110%
150%
170%
180%
180%
200%
8
100%
135%
150%
160%
160%
165%
10
90%
120%
135%
145%
145%
150%
12
78%
105%
120%
125%
125%
130%
14
67%
92%
104%
110%
110%
115%
16
57%
77%
87%
92%
92%
100%
Table 15: Overcurrent relative to time
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...