2 Assembly and installation
BU 0180 en-4118
57
In addition, care must be taken that a NORD motor from the motor list (P200) is set. If a standard
4-pole NORD motor or a motor from a different manufacturer is not used, the data for the motor
parameters ((P201) to (P208)) must be adjusted to those on the motor rating plate.
The stator
resistance of the motor (see P208) must be measured by the inverter and at ambient temperature. In
order to do this, parameter P220 must be set to "1".
In addition, the frequency inverter must be
parameterised so that the motor can be operated with a maximum speed of 3000 rpm. For a four-pole
motor, the "maximum frequency" must be set to a value which is smaller or equal to 100 Hz ((P105)
≤
100). Here the maximum permissible output speed of the gear unit must be observed. In addition,
the monitoring "I²t-Motor" (Parameter (P535) / (P533)) must be switched on and the pulse frequency
set to between 4 kHz and 6 kHz.
Overview of required parameter settings:
Parameter
Setting value
Factory setting
Description
P105
Maximum frequency
≤ 100
Hz
[50]
This value relates to a 4-pole motor. On
principle, the value must only be so large that
a motor speed of 3000 rpm is not exceeded.
P200
Motor list
Select appropriate
motor power
[0]
If a 4-pole NORD motor is used, the pre-set
motor data can be called up.
P201 – P208
Motor data
Data according to
rating plate
[xxx]
If a 4-pole NORD motor is not used, the
motor data on the rating plate must be
entered here.
P218
Degree of
modulation
≥ 100%
[100]
Determines the maximum possible output
voltage
P220
Parameter
identification
1
[0]
Measures the stator resistance of the motor.
When the measurement is complete, the
parameter is automatically reset to "0". The
value that is determined is written to P208
P504
Pulse frequency
4 kHz … 6 kHz
[6]
For pulse frequencies above 6 kHz a
reduction of the maximum torque is
necessary.
P533
Factor I
2
t-Motor
< 100%
[100]
A reduction in torque can be taken into
account with values less than 100 in the I²t
monitoring.
P535
I²t motor
According to motor
and ventilation
[0]
The I²t- monitoring of the motor must be
switched on. The set values depend on the
type of ventilation and the motor used. See
Содержание SK 180E Series
Страница 1: ...BU 0180 en NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters...
Страница 4: ...NORDAC BASE SK 180E SK 190E Users Manual for Frequency Inverters 4 BU 0180 en 4118...
Страница 185: ...8 Additional information BU 0180 en 4118 185 8 3 4 EU Declaration of Conformity...
Страница 211: ...Key word index BU 0180 en 4118 211...
Страница 212: ...6071802 4118...