NEW LEADER • NL5000G5 AGCO
Header
Controller Operations
•
Press
to set spinners. Enter appropriate
settings:
•
PWM Valve settings:
•
“Monitor” - no PWM control
•
“Control” - tries to maintain spinner speed at all
times regardless of available hydraulic flow. Best
for hydrostatic or CVT drives.
•
“Hold” - Preserves last PWM signal to valve
when conveyor is deactivated. Best for geared
transmitions with gear pumps.
•
PWM Frequency - Frequency that PWM control valve is pulsed at. Settings can be found from valve
manufacturer.
•
Zero Flow Offset - Represents maximum duty cycle sent to control valve without producing any hydraulic
flow from. Increase this number to hit target rate sooner.
IMPORTANT!
Setting Zero Flow Offset too high will cause spinners to overshoot Low Spinner Speeds and
could cause delay in reaching set speed. Adjust as needed in small increments.
•
PWM Gain - Determines how aggressively control valve responds when making rate adjustments. Higher
value means more aggresseive system response.
IMPORTANT!
Setting PWM Gain too high spinners will become erratic. Adjust as needed in small
increments.
•
Set Conveyors by selecting each bin at bottom of
screen.
NOTE:
If using PWM valves instead of Servo
valved, select “PWM” from “Control Valve
Type” list and enter settings as per notes
on Spinner valves and test for accuracy.
NOTE:
Restart is required if control valve type is
changed.