Option No.
Description
Default
P86E
1E
Disable Dialler
OFF
2E
Enable reporting by Contact ID
ON
P86E 1E
DisAbLE DiALLEr
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
Off: dialler enabled.
notEs
When should this option be used?
1. To temporarily prevent central station
reports and outgoing SMS messages
while testing the system. (Not essential
but useful)
2. To permanently disable the dialler if
using the panel without a SIM. (Highly
recommended)
Dialler buffer
Disabling the dialler also clears the
SMS and reporting queue. In addition,
the panel does not buffer any alarm
messages while the dialler is disabled
to prevent a flood of outgoing
messages once it is re-enabled.
signal strength indicator
While the dialler is disabled, the
keypad/s will show Signal Strength
level 0 (zero) even if a SIM card remains
fitted.
When this option is on the dialler is disabled even if telephone numbers and other dialler
options are programmed.
This option disables both incoming and outgoing communications. No alarm reports will be
sent and the dialler will ignore incoming SMS messages.
Turn this option on if you are using the panel as a local system without an active SIM card.
Leaving the dialler enabled without a SIM will generate unwanted dialler errors.
KPX+
P86E 1E to enable/disable the option
NAVIGATOR
P86E > enable/disable 1E
SMS*
P[MasterCode]E P[InstallerCode]E P86E 1E
Or use
NessXCEL
app
P86E 2E
EnAbLE rEPorting by ContACt iD
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
On: CID reporting enabled.
rELAtED oPtions
P170E Phone No 1 for CID reporting
P171E Phone No 2 for CID reporting
P87E 3E Enable reporting by SMS
notEs
The panel can send alarm reports to
a central station by CID or to mobile
phone number/s by SMS or both.
This option enables reporting to a central station in Contact ID (CID) format via CID phone
numbers programmed at P170E, P171E
KPX+
P86E 2E to enable/disable the option
NAVIGATOR
P86E > enable/disable 2E
SMS*
P[MasterCode]E P[InstallerCode]E P86E 2 E
Or use
NessXCEL
app
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
52
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g