Option No.
Description
P300E
DEFAULT ALL ACCESS CONTROL OPTIONS
DEFAULt ALL ACCEss ControL oPtions
Enter P300E in Installer program mode to return all access control programs to
factory default values.
PROGRAMMING ACCESS CARDS
If the panel has 1, 2 or 3 Weigand proximity readers connected up to 55 of the panel's
user codes can be programmed as Reader Codes. This allows arming/disarming by
access card and operation of AUX outputs to open electric door strikes.
Use the Extra Options programming mode to enable selected user codes to Readers
1, 2 or 3. When a user code is enabled as a Reader Code, its Keypad Code, (if any),
is automatically deleted. A user code enabled as a Reader Code cannot also be a
Keypad Code or Radio Code.
PROGRAMMING SEQUENCE:
In Installer Program Mode, enter the option number for the user code to be
programmed. (P202E–P256E).
KPX+
Press EXCLUDE E to enter Extra Options mode. (Exclude icon is on).
NaVIGaTOr
Press Extra Code Options.
KPX+
and
NaVIGaTOr
Press 6E, 7E or 8E to assign the user code to Reader 1, 2
or 3, or all three.
KPX+
EXCLUDE E to exit Extra Options mode. (The Exclude icon is off).
NaVIGaTOr
Press
to exit the Extra Options screen.
KPX+
Press 1E
(The OK icon will turn ON to indicate ready to accept the access card)
NaVIGaTOr
Press
If a code is already programmed the OK icon will not turn on and a warning beep will
sound. To clear the code, press 0E to clear existing codes then go back to step 5.
Present a valid access card to the reader.
If the card or fob is of a valid type, the reader's orange light will turn on.
If the card is accepted, the keypad OK icon will turn off and 3 beeps will sound.
If the OK icon stays on and a warning beep sounds, the access card is already
assigned to another user code and must be cleared from that code first.
PROGRAMMING ACCESS CARDS By SMS
SmS
Access cards can be programmed remotely by SMS as long as a person is on site to present the
card to the reader for programming.
Example, to program an access card as user 55.
The SMS string below enters program mode, selects user 55, assigns the code to readers 1,2
and 3, deletes any existing code, selects learn mode, then the panel will wait for 30 seconds
for a card to be enrolled. At this point you should present the card to a reader. Once the card is
successfully programmed you will hear 3 beeps from the keypad. The panel will exit program
mode on expiry of the 30 second learn window.
SMS*
P[MasterCode]E P[InstallerCode]E P255E XE6E7E8EXE 0E 1E
When the keypad displays
READy TO RECEIVE / OK
, present the card to a reader.
RF Card
If connecting multiple readers, the
option to enable multiple readers
(P301E 1E) should be turned on
before
programming any access cards.
(Enabling P301E 1E erases existing card
programming).
Z8
Zone 8 Input
NORMALLY OPEN
Momentary pushbutton
C
Z8
Zone 8 Input
NORMALLY CLOSED
Momentary pushbutton
C
If P301E 3E is enabled, a
momentary push button can be
wired to zone 8 as shown.
For example, this option allows the reader
output to operate a door lock during the
day by presenting your card. Then at the
end of the day press the push button
within 5 seconds of presenting the card
and the panel will arm.
P300E
ProgrAm moDE LEVEL
Installer
rELAtED oPtions
P301E 2E Allow arming with a double read
P301E 3E Allow arming with a single read
and pushbutton.
P301E 4E Allow disarming, (single read).
Separate options for arming & disarming
allows 'arm only' permission to be granted if
required.
P121E 8E, P122E 8E, P123E 8E and
P124E 8E to enable readers to operate AUX
outputs.
P301E 1E Use Reader Addresses allows up
to 3 Ness 101-014 Ultraprox Readers to be
used with individual addresses.
P318E - P338E Assign readers to AUX
outputs.
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
81
ACCEss ControL
NESS D8X / D16X DELUXE CONTROL PANEL – INSTALLATION MANUAL