Option No.
Description
Default
P66E
1E
Zone Supervision alarm to RESET output
OFF
2E
Zone Supervision alarm to STROBE
OFF
3E
Zone Supervision alarm to SONALERT
OFF
4E
Zone Supervision alarm to SIREN
OFF
5E
Enable WIRED ZONE supervision
OFF
6E
OFF
7E
Zone Supervision speedup x 6
OFF
8E
Zone Supervision speedup x10
OFF
P66E 1E
ZonE sUPErVision ALErts – rEsEt oUtPUt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: Supervision Reset output
disabled.
rELAtED oPtions
P65E Supervised Zones.
Setting this option turns the Reset output ON when a SUPERVISED ZONE alert occurs. The
Reset output will remain ON for the duration of the ALARM TIME (Set by Option P29E).
KPX+
P66E 1E to enable/disable the option
NAVIGATOR
P66E > enable/disable 1E
SMS*
P[MasterCode]E P[InstallerCode]E P66E 1E
Or use
NessXCEL
app
P66E 2E
ZonE sUPErVision ALErts – strobE oUtPUt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: Supervision Strobe output
disabled.
rELAtED oPtions
P65E Supervised Zones.
Setting this option turns the Strobe output ON when a SUPERVISED ZONE alert occurs.
The Strobe output will remain ON until the panel is disarmed.
KPX+
P66E 2E to enable/disable the option
NAVIGATOR
P66E > enable/disable 2E
SMS*
P[MasterCode]E P[InstallerCode]E P66E 2E
Or use
NessXCEL
app
P66E 3E
ZonE sUPErVision ALErts – kEyPAD sonALErt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: Supervision Keypad Sonalert
disabled.
notEs
When this option is turned ON, it delays
the operation of all other selected
Supervision outputs by one minute.
rELAtED oPtions
P65E Supervised Zones.
Setting this option turns the Keypad Sonalert ON when a SUPERVISED ZONE alert occurs.
The Keypad Sonalert remains ON until
any
keypad key is pressed.
Also, turning this option ON makes all Supervision outputs delayed by one minute.
KPX+
P66E 3E to enable/disable the option
NAVIGATOR
P66E > enable/disable 3E
SMS*
P[MasterCode]E P[InstallerCode]E P66E 3E
Or use
NessXCEL
app
P66E 4E
ZonE sUPErVision ALErts – sirEn oUtPUt
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
OFF: Supervision Siren output disabled.
rELAtED oPtions
P65E Supervised Zones.
Setting this option turns the Siren output ON when a SUPERVISED ZONE alert occurs. The
Siren output will remain ON for the duration of the ALARM TIME (Set by Option P29E).
KPX+
P66E 4E to enable/disable the option
NAVIGATOR
P66E > enable/disable 4E
SMS*
P[MasterCode]E P[InstallerCode]E P66E 4E
Or use
NessXCEL
app
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
40
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g