P129E
1E
0k EOL resistors
OFF
2E
1k EOL resistors
OFF
3E
1.5k EOL resistors
OFF
4E
2.2k EOL resistors
ON
5E
3.3k EOL resistors
OFF
6E
3.9k EOL resistors
OFF
7E
4.7k EOL resistors
OFF
8E
5.6k EOL resistors
OFF
9E
6.8k EOL resistors
OFF
10E
8.2k EOL resistors
OFF
11E
10k EOL resistors
OFF
12E
12k EOL resistors
OFF
13E
22k EOL resistors
OFF
P126E
1E
Enable Double key PANIC
ON
2E
Enable Double key FIRE
OFF
3E
Enable Double key MEDICAL & Nav MEDICAL
OFF
4E
Enable Entry Chime, DAy Mode
OFF
5E
Enable Entry Chime, HOME Mode
OFF
8E
Disable One Digit At A Time display
ON
P126E
misC kEyPAD oPtions
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
1E on. Double key Panic enabled.
2E – 5E off.
8E on.
notEs
• One or all options can be enabled.
• To operate KPX/Saturn double key
functions - in normal operating mode
press and hold the matching keys for at
least 1.5sec.
Various programming options for Ness KPX+, Saturn and Navigator keypads.
KPX+
P126E xE to enable/disable an option as required
NAVIGATOR
P126E > enable/disable an option as required
SMS*
P[MasterCode]E P[InstallerCode]E P120E 1E
Or use
NessXCEL
app
1E KPX & SATURN. Enables double key PANIC. (Both PANIC Keys together)
2E KPX & SATURN. enables double key FIRE. (Both FIRE keys 1, 3, together)
3E KPX & SATURN. Enables double key MEDICAL (Both MEDICAL keys 4, 6, together) and
enables MEDICAL on Navigator.
4E Enables Entry Chime in Day mode. Used to announce entry in Day mode.
5E Enable Chime in Home Mode. Used to announce entry in Home mode.
8E Disable One Digit At A Time Display. This allows Navigator keypads to immediately display
numeric options.
P129E
EnD oF LinE rEsistor oPtions
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
4E, 2.2k
notEs
• Only one option can be on. Turning
an option on turns off another.
• The EOL value selected applies to
all zone inputs and the external tamper
input, except the keyswitch input which
is always 2K2.
• The keyswitch input (if enabled)
always uses a 2K2 resistor regardless
of the global EOL resistor value set by
P129E.
Also see P60E 2E, 3E, page 33.
The End Of Line Resistor value for all zones and the external tamper can be programmed
with one of 13 different resistor values.
This allows the panel to be easily retro-fitted into almost any existing installation.
KPX+
P129E xE to select one option as required
NAVIGATOR
P129E > select one option as required
SMS*
P[MasterCode]E P[InstallerCode]E P129E xE
Or use
NessXCEL
app
73
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g