Option No.
Description
Default
P89E
1E
ENABLE TEST CALLS
ON
2E
Mains Report Delay (1 hour)
ON
3E
[not used]
OFF
4E
Swinger shutdown
ON
5E
Line Fault Monitor
OFF
6E
Master Code Clears Dial Attempts
OFF
7E
[not used]
OFF
8E
[not used]
OFF
P89E 1E
EnAbLE tEst CALLs
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
ON: Test Calls enabled.
rELAtED oPtions
P83E Test Call Interval.
P84E Time before next Test call.
P87E 4E Number Of Dialling Attempts.
notEs
Test Calls cannot be sent by SMS, only
to a central station.
Enables the reporting of dialler test calls to the Central station.
KPX+
P89E 1E to enable/disable the option
NAVIGATOR
P89E > enable/disable 1E
SMS*
P[MasterCode]E P[InstallerCode]E P89E 1E
Or use
NessXCEL
app
P89E 2E
mAins rEPort DELAy
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
ON: Mains Fail report is delayed.
Allows Mains Fail reports to be delayed by one hour if the mains power has been off
continuously for that time. This avoids mains fail reports being sent to the Central Station
in the event of brief power failures.
KPX+
P89E 2E to enable/disable the option
NAVIGATOR
P89E > enable/disable 2E
SMS*
P[MasterCode]E P[InstallerCode]E P89E 2E
Or use
NessXCEL
app
P89E 4E
sWingEr shUtDoWn
ProgrAm moDE LEVEL
Installer
FACtory DEFAULt
ON: Swinger Shutdown enabled.
notEs
This prevents unnecessary multiple
alarms reported to the Central station
in cases, for example, where a door is
‘swinging’ in the wind.
This option only applies to zones
enabled to Report Multiple Zone
Alarms.
rELAtED oPtions
P78E Report Multiple Zone Alarms.
Limits the number of calls made by a zone alarm in any one armed period. Alarm reports
are normally limited to 15 multiple reports per zone. When Swinger Shutdown is enabled,
multiple reports are reduced to 3 multiple reports per zone.
KPX+
P89E 4E to enable/disable the option
NAVIGATOR
P89E > enable/disable 4E
SMS*
P[MasterCode]E P[InstallerCode]E P89E 4E
Or use
NessXCEL
app
* SMS programming shows the full SMS string to send. KPX+ and
NAVIGATOR programming assumes the panel is already in program mode.
56
NESS D8XCEL / D16XCEL CONTROL PANEL – INSTALLATION MANUAL REV 1.1
P r o g r A m m i n g