82
Service
GB
SUPREMATouch
12
node guarding
error detected
MCP, MDO
Module does not
respond to
node- guarding,
or does not send
any heartbeat
All nodes
respond again
X
X
ID of node
that doesn’t
respond
If the node in
info 1 is an
MDA and
info 2 is not
0, this is the
MAI number
CAN bus failure,
module defect or
missing: Check
bus and modules
MGO, MAO
X
X
Always 0
Time in
system-ticks
no output data was
received for a
certain time: check
bus and MCP/
MDO modules
13
program error
MCP, MDO,
MBC
Application
program error
Restart
X
X
Application
error code
Additional
data (error
code
depended)
Normally software
problems (not
plausible internal
software status) or
invalid MAC
address
14
data error
MCP, MDO
Application data
error
Restart
X
X
Application
error code
Additional
data (error
code
depended)
Normally software
problems (not
plausible internal
software data)
Often sequence
error of No. 9 or 10
15
system configura-
tion error
MCP, MDO
The system
configuration
detected does
not correspond
to the configura-
tion stored or
configuration/
parameteriza-
tion is not
consistent
Restart
X
X
Configura-
tion error
code
Additional
data (error
code
depended)
Modules on wrong
plug position?
Several racks of
the same ID
(switch) in the
system?
MAI30,
MGI30,
MAR30,
MGR30
Module in invalid
slot
Restart
X
X
Slot number Always 0
The module is in
an invalid slot
MAO, MGO
Module in invalid
slot
Restart
X
X
Always 0
Always 0
The module is in
an invalid slot
16
data acquisition
error
MAI30,
MGI30,
MAR30,
MGR30
communication
error of onboard
communication;
invalid test
values;
No communica-
tion or not
matching
measuring
values on
primary and
secondary
module
All errors gone
X
X
error code
Additional
data (error
code
depended)
MAI30 / MGI30 or
MAR30 / MGR30
defect.
MGO
SPI communica-
tion error at
digital outputs
(MGO)
SPI communica-
tion respectively
outputs all right
again
X
X
1-5
→
number of
erroneous
output block
FF
→
hard-
ware defect
MGO: diag-
nosis code
Outputs short
circuited or open
or module defect.
No.
Fail Message
Text
Module
Appears in
case of
Disappears in
case of
Error
LED
Fail
LED
Info 1
Info 2
Remarks/ Reme-
dial action
(BYTE)
(DWORD)
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...