124
Installation
GB
SUPREMATouch
(4) Depending on the type of system shipped, install the switch cabinet, or the 19” mounting
rack.
(5) Check the configuration of the modules and reconfigure if necessary.
(6) Install the modules in the 19” mounting rack (unless already installed at the factory).
a) If possible, fix the modules to the back with screws (1 Nm torque).
(7) In case of expanded systems with more than one 19” mounting rack, connect the CAN bus
or check the connection if it has already been made.
(8) Install the sensors and connect the wiring to the SUPREMATouch.
(9) Connect the relay and current outputs to the external devices to be actuated.
(10) Connect the current and voltage supply.
(11) After installation is complete, perform the start-up procedure as instructed in Chapter 13
12.4 Unpacking
Perform the following steps on receipt of the shipment:
(1) Carefully unpack the device or its components, observing all of the instructions printed on or
accompanying the packaging.
(2) Inspect the contents of the delivery to determine if any transport damage has occurred and
verify that everything listed in the shipping papers has in fact been received.
12.5 Cabling
The terminal posts on the
analogue Terminal Units
(MAT module and MAT TS module) are
designed for the connection of conductors with a cross section in the range of 0.2–1.5 mm
2
.
The terminal posts on the
Relay Output Units
(MRO8, MRO8 TS, and MRO16 TS modules) are
designed for the connection of conductors with a cross section in the range of 0.2–2.5 mm
2
.
The terminal posts on the
External Connection Module MGT40 TS
are designed for the connec-
tion of conductors with a cross section in the range of 0.2–2.5 mm
2
.
On the
Interconnection Board
(MIB module), the terminal posts for the connection of the supply
voltages are designed for conductor cross sections of 0.2–4.0 mm
2
, and the terminals for the
system fail relays are designed for conductor cross sections of 0.14–1.5 mm
2
.
On the
System Terminals Module
(MST module), the terminals for Alarm Reset, Horn Reset,
Relay Inhibit, and Key Switch are designed for conductor cross sections in the range of 0.2–
2.5 mm
2
. The
System Terminals Module
(MST module) also has 2 SUB-D plug connector strips
(9-way) for the connection of the CAN bus and 3 SUB-D socket terminal strips for RS232 connec-
tions.
The terminals for the supply voltage on the
Relay Connection Module
(MRC TS module) are
designed for conductor cross sections of 0.2–2.5 mm
2
.
The modules installed separately from the rack (MAT TS, MRC TS, and MGT40 TS modules) and
the Universal Terminal Module (MUT module) are connected with a 40-way screened ribbon
cable. The Relay Connection Module (MRC TS module) is connected to the Relay Output
Modules (MRO8 TS, MRO16 TS) by a 20-way ribbon cable.
If possible, fix the modules on the back with screws (torque: 1 Nm).
Allowed Conductor Cross Sections
Module
Conductor Cross Section
MAT/MAT TS Module
0.2 mm
2
–1.5 mm
2
MRO8/MRO8 TS/MRO16 TS Module
0.2 mm
2
–2.5 mm
2
MRC TS Module (Supply Voltage, Relay Lock)
0.2 mm
2
–2.5 mm
2
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...