69
Entering System Parameters
GB
SUPREMATouch
Processor Temperature Logbook
This logbook stores the over-limit and under-limit temperature events for the analog input
modules. When the temperature goes above or below the permitted range, the current tempera-
ture value is stored, and when it returns to within the permitted range, the peak value from the
deviation is stored.
Each entry includes the following data:
• Date/Time of the over-limit or under-limit event
• Serial number of the analog input module
• Node ID and bus of the module
• Temperature value (0 - 55 °C)
• Information on whether it remained out of the permitted range or returned to it
Measuring Points
This displays the current signal measurement values of one input.
Fig. 47 Measuring Points
Field
Field Type
Function
Measuring
Point No.
Selection
After selection of a measuring point number, the current signals
of the selected point are displayed.
Signal U
A
Display
The amplified sensor signal is displayed in these fields sepa-
rated by bus.
When transmitters are used, 4 mA equal 400 mV.
Signal U
Q
Display
When passive detectors are used, the bridge current is
displayed as a voltage value (1 mV equals 1 mA) in these field
separated by bus. When active transmitters are used, the draw
current is shown similarly.
Signal U
Y
Display
When passive detectors are used the amplified sensor signal
U
Y
is displayed in these fields separated by bus. The signal
consists of a fixed gain that depends on the detector type used
and an offset voltage.
When active transmitters are used, these fields are empty.
Signal U
x
Display
When passive detectors are used, the measured U
X
signal is
displayed in these fields, separated by bus. When transmitters
are used, these fields are empty.
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...