213
Sensor Data
GB
SUPREMATouch
Simulation of normal operation / Alarm / RESET / Open or short-circuit fault indication:
Conditions for use
Mounting
Wall mounting
Ingress protection
IP 54 according to DIN 400 50
Explosion protection
yes
Certificate
BASEEFA 03ATEX0084X
Temperature
-20 °C to +55 °Cv
Humidity
-
Pressure
-
Weight
approx. 1100 g
Dimensions
120 x 125 x 75 mm
Housing material
Aluminium, pressure-resistant
Simulation
Effect
Normal operation
External power supply 23–32 V
connected according to circuit diagram
END OF LINE resistor 2K2connected according to circuit
diagram
Connect resistor 10 K 0.5 W
between terminal 1 and 2
Normal operation
Voltage of terminal 1–2 shall be <0.1
V
Alarm
External power supply 23–32 V connected according to
circuit diagram
END OF LINE resistor 2K2 connected according to circuit
diagram
Connect resistor 1.0 K 1% 0.5 W between terminal 3 and 44
Alarm message
RESET
Connect wire jumper between terminals 3 and 4
Normal operation
After max. 45 s failure message
appears.
Open-circuit of line
External power supply 23–32 V connected according to
circuit diagramEND OF LINE resistor 2K2 not connected
Failure message
Line short-circuit
External power supply 23–32 V connected according to
circuit diagram
END OF LINE resistor short-circuited
Failure message
Interruption of the supply voltage
External power supply 23–32 V not connected END OF
LINE resistor 2K2 connected according to circuit diagram
Failure message after max. 45 s
Leakage current
External power supply 23–32 V connected according to
circuit diagramEND OF LINE resistor 2K2 connected
according to circuit diagramConnect resistor 10 K 0.5 W
between terminal 1 and 2Connect resistor 18 K between
terminals 4 and 5, or connect resistor 330R between termi-
nals 3 and 5.
Failure message
Voltage of terminals 1–2 shall be
>22
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...