Entering System Parameters
GB
SUPREMATouch
Head Parameters
Fig. 30 Head parameter
This window displays the significant parameters of the remote sensors. During normal operation
the SUPREMATouch software continuously checks the detector output signal sent to the
SUPREMATouch. In case the detector output signal falls below UA
min
an inhibit indication, and
below UA
idle
a fault indication will be set for this measuring point. In case the detector output signal
exceeds UA
over
an overflow will be indicated. Data fields that are not used for a specific remote
sensor are empty.
It is possible to enter user specific data for some active remote transmitters (4–20 mA signal). For
this purpose, the following fields can be changed: Name (English and local language), UA
min
,
UA
idle
, UA
over
and T
supp
. The
ID
of modifiable remote sensors begins with the value
10000
and
their status is displayed as
changeable
.
Field
Field Type Function
ID (Remote sensor
ID)
Selection
A remote sensor can be selected by its ID
Status (Status of
this data cell)
Display
Displays the status of the cell used for data saving. If this
status is
protected
, then no data can be changed and the
following input fields are simply display fields.
2 x Name (Head
name in English
(upper) and local
language (lower)
Text, 16
characters
In these fields, the name of the remote sensor is displayed in
both supported languages. The remote sensor can be
selected as
Sensor type
in the setting of the measuring points
through these names.
The user can freely define the names in changeable remote
sensors. They must be unique, that is, no name can be given
twice. If a name is given for only one language, the same
name can also be used for the other language while saving it.
UA
min
(Limit for
“suppressed”)
Number
(integers)
Adjusting
range: 50–
350
To leave empty, press clear
This field displays the maximum signal UA for the status
suppressed
. Measuring values below this limit value are
displayed as
suppressed
. If field is empty (tap
Clear
in the
number input window), then this status will not be tested.
This value can only be set for the three user-changeable data
sets.
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...