118
Modules
GB
SUPREMATouch
connected by plugging in “terminal modules” (MAT module, MUT module, etc.) at the rear of the
rack.
• Rack rear-panel wiring for 2 x MCP modules, 1 x MDC+MDO module, 2 x MDA modules (to be
downward compatible), 8 x MAI/MGO/MAO/MBC modules, and additional 2 x MGO/MAO/
MBC modules
• Power supply for all modules (INT, EXT, BAT)
• Connections for 3 x 24 VDC power supplies, screw terminals (4 mm
2
)
• Provides uninterruptible 24-V-system power
• Data transfer between the modules over the CAN bus or the SPI bus
• 2 system error relay, 1 change-over contact, 3 connecting terminals
• DIL switch for CAN rack ID, CAN bus termination, system behaviour (Free A/B) and baud rate
• Electric connection for the inserted modules
• Terminal or connection modules (MST, MAT, MUT etc.) are plugged into the rear of the MIB
module
MST Module (System Terminals)
• Connection module for system expansions.
• Installed at the rear of the rack.
• Ports MST10: 2 x CAN A, 2 x CAN B, RS232-A (PC operation), RS232-B (serial printer, output
of messages), RS232-C (unused), alarm reset (RES), horn acknowledge (HACK), relay inhibit
(LOCR), password key switch (PSW).
• Ports MST20: 2 x CAN A, 2 x CAN B, RS232-A (PC operation), RS232-B (serial printer, output
of messages), USB (PC operation), Ethernet, alarm reset (RES), horn acknowledge (HACK),
relay inhibit (LOCR), password key switch (PSW).
MAT Module (analogue Terminal Module)
• Connecting terminals for remote measuring heads
• Terminals for sensors, 4–20 mA outputs, etc. (1.5 mm
2
)
• 8 inputs, each with 5 terminal connections
• Up to 4 MAT modules can be provided for the connection of up to 32 sensors
MAT Module TS (analogue Terminal Module)
Similar to the MAT module but for installation on C-type or top-hat rail separate from the rack.
A 40-way ribbon cable and a MUT module are required to connect it to the rack.
MUT Module (Universal Terminals)
This module is used to connect modules which are separate from the rack (MRC TS module,
MAT TS module, etc.) to the module inserted in the rack with a 40-way ribbon cable.(Adapter plug,
96-way to 40-way.)
Relay Outputs
Up to 512 switching outputs can be controlled by the system via MGO modules (40 open collector
drivers each). These switching outputs can be used to drive relays, magnetic valves, contactors,
lamps, LEDs (24 VDC/0.3 A). If relay outputs are required, various relay modules can be used:
MRC TS module
Relay connection, actuation of 5 relay modules
MRO8 module
8 common alarm relays on the rack
MRO8 TS module
8 relays, installed on mounting rail
MRO8 SSR TS
Optional 8 solid state relays, installed on mounting rail
(for very low current switching applications)
MRO16 TS module
16 relays, redundant layout, installed on mounting rail
MRO16 SSR TS
Optional 16 solid state relays, redundant layout, installed
on mounting rail (for very low current switching applica-
tions)
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...