212
Sensor Data
GB
SUPREMATouch
16.10 Explosion-proof Push-Button Detector with Barrier Z 787
Fig. 141
The cable screen is only connected to the SUPREMA.
Simulation
Effect
Normal operation
END OF LINE resistor 2K2connected according
to circuit diagram
Normal operation
Alarm
END OF LINE resistor 2K2 connected according
to circuit diagramConnect resistor 1.0 K 1% 0.5
W between terminals 3 and 4
Alarm message
RESET
Connect wire jumper between terminals 3 and 4
Alarm message disappears, normal opera-
tion.After max. 45 s failure message appears.
Open-circuit of line
END OF LINE resistor 2K2 not connected
Failure message
Line short-circuit
END OF LINE resistor short-circuited
Failure message
*1
Connect push-button detector according to manufacturer’s specification;
MEDC NG16 6JF Type BGI WIRING DIAGRAM BGE/I/W + PBE/IW
Contact type: NORMALLY OPEN (terminal 2–3 inside the detector)
Carry out installation according to NFPA 72
•
With resistor 2.2 kOhms / 0.5 W in series with the contact; max. 10 Pieces
•
With zener diode 10 V / 1.3 W in series with the contact; max. 20 Pieces
Check polarity
*2
End of Line Resistor 2K2 / 0.5 W to be mounted in the last mounting support of the detection zone circuit or in the portable detector
according to the documents specified under *1.
*3
Indication of leakage current. In case of failure, the “OPEN COLLECTOR“ transistor is conducting to terminal 5
Connection module:
MAI30
Connection data
Maximum nominal current
42 mA
Maximum nominal voltage
22 V
Power consumption
≤
1.5 W (including cable length)
Cable type
2-core, 80 % screened
Maximum loop resistance
50 ohms (cable resistance)
Maximum cable length
2000 m (1.5 mm
2
cross section per wire)
Cross section per wire allowed
0.5–2.5 mm
2
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...