2.6
Bus Protocol
The SUPREMATouch uses the CAN bus protocol. On the Interconnection Board (MIB module),
the DIL switch can be used to set the transfer speed to 10, 20, 50, 125, 250, 500 or 1,000 kBits/s
for all of the connected modules. All modules on one bus must operate at the same bit rate; if one
of the modules uses a different rate, an error state occurs on the bus. This is detected, and appro-
priate messages are displayed.
Each module receives a code (Node ID) in the range of 1–127 by the use of the DIL switch of the
MIB module board on the basis of its slot in the rack. Each of the modules on one bus must have
its own code. If duplicate codes are detected, an error message is generated.
2.7
System Power Supply
The system is supplied with an operating voltage of 24 VDC (19.2–32 VDC). 3 pairs of terminals
for the connection of three 24 VDC power supply sources (EXT, INT, BAT) are provided on the
Interconnection Board (MIB module). Therefore the power can be taken from 3 different sources
(redundancy). If all three supply voltages (EXT, INT and BAT) are present, the system selects
only one of these to supply the module, in the following order of prioritisation:
1st = EXT, 2nd = INT, 3rd = BAT.
The system module hardware manages the power supply changeover.
When an external power pack or battery supply is used, MSA recommends that the power is
filtered through an appropriate EMC (electromagnetic compatibility) filter. See chapter 12.2
"Installation Instructions for Following the EMC Directives"for low voltage installation information.
In order to protect the battery and the SUPREMATouch against damage, an additional deep
discharge contactor component is required in the corresponding 24 V feeder (e.g. deep discharge
contactor C1900-TLS, Mentzer or similar).
• The customer is responsible for providing a safety cut-out (maximum rack power, 480 W/20 A).
• 85–264 VAC is supplied via screw terminals directly on the power supply unit.
• The EXT, INT and BAT voltages are supplied to each system module.
• Voltages required for the individual modules are obtained in the modules themselves from the
24 V.
• The power requirement that must be met is derived from the type and number of sensors
connected and from the components installed in the system.
• Maximum power provided for one rack is 480 W (maximum current of 20 A).
• The transmitter/detector input modules measure all input voltages and can generate error
messages, which can be shown on the display unit. In addition, a POWER FAIL relay
(optional: redundant) is de-energized when the status of the system power supply changes.
EXT Terminals (External Power Supply, 24 VDC)
• Connection for voltage supply from an external power supply unit; power is sent to all units in
the rack.
• Required when a redundant power supply is provided or when the internal rack power supply
is not sufficient to operate all of the sensors.
• Maximum supply current of 20 A for one rack.
SIGNAL:
AL 1–AL 4
(red)
input signal alarms
(each input can have up to four alarms)
FAIL
(yellow)
specific input signal statuses
(measurement values that are over full-scale, below the measurement
range and signal failures)
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...