172
Installation
GB
SUPREMATouch
Plug Assignment:
Tab. 110 MST Module, Pin Assignment, CAN Bus Ports
Only screened (>80 % coverage) CAN-cables may be used. These must have separate cable
screen, which is connected to the plug housing. A wire is to be provided in the cable for the CAN
GND.
PC/Laptop Port (System Operation, RS232A/USB)
A PC or a laptop can be plugged into this port. By using the SUPREMATouch operating program,
the system can be operated with a Windows interface. This is recommended, especially for the
initial setup of a new system with an average or large number of inputs (Chapter 14.1 "Connecting
a PC/Laptop"), It also makes it easier to perform calibrations and routine maintenance. The PC/
laptop should meet the following minimum requirements:
The terminal assignment of the RS232A connection is given in the following table (see Tab. 111
"RS232A Terminal Assignment"). Connect the screening to the pin housing.
Tab. 111 RS232A Terminal Assignment
Printer Port (Printer, RS232 B)
Using this port, the alarm messages can be sent to a printer so that records can be kept.
Plug
Name
Terminal No.
Assignment
X13, X15
CAN A
2
CAN_L
3
GND
6
GND
7
CAN_H
X14, X16
CAN B
2
CAN_L
3
GND
6
GND
7
CAN_H
System Requirements for PC:
- Minimum Pentium IV, 2GHz, 2 GB of RAM
- Windows XP SP 3
- Connecting cable USB: miniUSB / RS232: RS232 extensions, SUB-D connector 9-way,
plug and socket (do not use a null-modem cable!)
- RS232 configuration: 19200/115200 kBits/sec., 8 data bits, 1 stop bit, Parity none
Socket No.
Assignment
1
2
TxD
3
RxD
4
5
GND
6
7
8
9
- Connecting cable: RS232 extension (do not use a null-modem cable!)
- RS232 configuration: 19200 kBits/sec., 8 data bits, 1 stop bit, Parity none
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...