Entering System Parameters
GB
SUPREMATouch
Information subwindow
Fig. 21 Information subwindow
Field
Field Type
Function
Tag
Text, 10 charac-
ters; empty by
default
Enter a customer-specific designation for the selected relay
output.
Normal Run
(Normally ener-
gised/Normally
de-energised)
Selection,
default is closed-
circuit
Set the operating mode for the selected relay output:
• Normally energised (
closed circuit
): The relay coil is
energised in the no alarm status and is de-energised in
the alarm status.
The output delivers in the set-condition (Alarm, Failure)
a LOW-Signal, this is called a connected relay is not
energised. (The Normally energised principle)
• Normally de-energised (
open circuit
):
The relay coil is de-energised in the no alarm status and
is energised in the alarm status.
The output delivers in the set-condition (Alarm, Failure)
a HIGH-Signal, this is called a connected relay is ener-
gised. (The Normally de-energised principle)
blinking
Checkbox, not
set by default
If enabled, the relay flashes at a frequency of approx.
0.5 Hz when activated until the alarm is acknowledged. This
function doesn't work combined with the inhibit condition.
Point based
voting
Checkbox, not
set by default
If enabled, the counting for the voting is done by counting
the effected measuring points instead of the effected condi-
tions.
New Alarm
Checkbox, not
set by default
If this field is set, the relay output selected can be set to the
status defined by the input field Normal Run by acknowl-
edging the selected conditions, even if the conditions are
still pending.
Delay
Integer, Range
is 0 to 10; 0 by
default
Defines a delay between the occurence of the switching
conditions for this output and the actual switching of the
output.
Time delays for relays should not be used for safety-relevant purposes. If the use
cannot be avoided, the minimum possible value for the given application must be set.
Содержание SUPREMATouch MCP 20
Страница 1: ...MSAsafety com Operating Manual SUPREMATouch Fire and Gas Warning Unit Order No 10121863 05...
Страница 8: ...MSAsafety com User Instruction Manual SUPREMATouch Fire and Gas Warning Unit...
Страница 72: ...MSAsafety com Service and Maintenance Guide SUPREMATouch Fire and Gas Warning Unit...
Страница 101: ...8645 Rapperswil Jona Switzerland info ch MSAsafety com www MSAsafety com MSA 2017 All rights reserved...
Страница 232: ...232 Dimensions GB SUPREMATouch 18 Dimensions 18 1 Rack...
Страница 233: ...233 Dimensions GB SUPREMATouch 18 2 Rail mounted Modules MRO8 TS Module MRO16 TS Module...
Страница 235: ...235 Dimensions GB SUPREMATouch MRO20 8 TS Module 1 3 2 69 90...
Страница 236: ...236 Dimensions GB SUPREMATouch MRO20 16 TS Module 2 5 2 64 73 relay dependent 90...
Страница 237: ...237 Dimensions GB SUPREMATouch MRC TS Module MGT40 TS Module...
Страница 238: ...238 Dimensions GB SUPREMATouch MHD TS Module MAT TS Module...
Страница 241: ...For local MSA contacts please visit us at MSAsafety com Because every life has a purpose...