background image

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: [email protected]

EM-5042  Rev.9  P. 1 / 3

INSTRUCTION MANUAL

Mini-M

DC ALARM

(thumbwheel switch adjustment)

MODEL

M2SED

BEFORE USE ....

Thank you for choosing M-System.  Before use, please check 
contents of the package you received as outlined below.
If you have any problems or questions with the product, 
please contact M-System’s Sales Office or representatives.

 

PACKAGE INCLUDES:

Signal conditioner
(body + base input resistor)..................................(1)
Input resistor is provided only with current input type.

 

MODEL NO.

Confirm Model No. marking on the product to be exactly 
what you ordered.

 

INSTRUCTION MANUAL

This manual describes necessary points of caution when 
you use this product, including installation, connection and 
basic maintenance procedures.

POINTS OF CAUTION

 

CONFORMITY WITH EU DIRECTIVES, UK LEGISLATION OR UL

• This equipment is suitable for Pollution Degree 2, Meas-

urement Category II (output, transient voltage 2500V) 
and Installation Category II (transient voltage 2500V).  
Reinforced insulation (signal input or output to power in-
put: 300V) and basic insulation (signal input to output: 
300V) are maintained.  Prior to installation, check that 
the insulation class of this unit satisfies the system re-
quirements.

• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate 

clearance and creepage distances are maintained to con-
form to CE/UKCA/UL requirements.  Failure to observe 
these requirements may invalidate the CE/UKCA/UL 
conformance.

• The actual installation environments such as panel con-

figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated 
in a panel system.  The user may have to review the CE/
UKCA requirements in regard to the whole system and 
employ additional protective measures to ensure the CE/
UKCA conformity.

• Install lightning surge protectors for those wires connect-

ed to remote locations.

 

POWER INPUT RATING & OPERATIONAL RANGE

• Locate the power input rating marked on the product and 

confirm its operational range as indicated below:

    100 – 240V AC rating: 85 – 264V (90 – 264V for UL), 
     

 

 

 

        47 – 66 Hz, approx. 3 – 5VA

    24V DC rating: 24V ±10%, approx. 3W
    11 – 27V DC rating: 11 – 27V, approx. 3W
  110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W

 

GENERAL PRECAUTIONS

• Before you remove the unit from its base socket or mount 

it, turn off the power supply and input signal for safety.

 

ENVIRONMENT

• Indoor use.
• When heavy dust or metal particles are present in the 

air, install the unit inside proper housing with sufficient 
ventilation.

• Do not install the unit where it is subjected to continuous 

vibration.  Do not subject the unit to physical impact.

• Environmental temperature must be within -5 to +55°C     

(23 to 131°F) with relative humidity within 30 to 90% RH 
in order to ensure adequate life span and operation.

• Be sure that the ventilation slits are not covered with ca-

bles, etc.

 

WIRING

• Do not install cables close to noise sources (relay drive 

cable, high frequency line, etc.).

• Do not bind these cables together with those in which 

noises are present.  Do not install them in the same duct.

 

AND ....

• The unit is designed to function as soon as power is sup-

plied, however, a warm up for 10 minutes is required for 
satisfying complete performance described in the data 
sheet.

COMPONENT IDENTIFICATION

Input Resistor

3 1

4 4

Body

Base Socket

Connection

Diagram

Specifications

Fixing Screw

 

FRONT PANEL CONFIGURATION

The front cover cannot be turned open by 180 deg. 
when there is no extra space between units.

Output 1 Setpoint Adj.

Output 2 Setpoint Adj.

Output 1 Monitor LED

Output 2 Monitor LED

9 9

9 9

Отзывы: