5 Commissioning
Maschinenfabrik Reinhausen GmbH 2016
67
5163667/00 EN
TRAFOGUARD® ISM®
Assembly
Interfaces
Test parameters
max. test volt-
age
max. test du-
ration
Ramp
Breaking cur-
rent threshold
DIO 28-15
DIO 42-20
DIO 42-20 HL
2.2 kV AC
2 s
5 s
any DI, DO
> 1 mA
G1 (PULS)
N, L
> 4 mA
Table 8: Permitted interfaces and test parameters for the high voltage test
1)
only the version with 85...265 VAC/VDC wide-range power supply, other-
wise the device may be damaged. Note the nameplate.
Sample set-up of the high voltage test
Figure 64: Sample set-up of the high voltage test for a device designed with the OT 1205 wide-range power supply