6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
175
5163667/00 EN
TRAFOGUARD® ISM®
Setting the time zone
If the time information is conveyed to the device by a network service (SNTP
or SCADA), this time is transferred depending on the set reference time
[
175]. To adjust the device time to your local time, you can use the time
shift parameter to set the time shift to UTC.
Example:
Region
Time shift to UTC
Mumbai, India
UTC +5:30 h
Beijing, China
UTC +8:00 h
Rio de Janeiro, Brazil
UTC -4:00 h
Table 36: Time shift to UTC (Coordinated Universal Time)
To set the time zone, proceed as follows:
1.
Go to
Settings > Parameters > Time synchronization > Time zone
.
2.
Select the option you want.
3.
Press the
Accept
button to save the modified parameter.
Setting synchronization interval
You can use this parameter to set the interval at which the device is to call
up the time from the time server.
To set the synchronization interval, proceed as follows:
1.
Go to
Settings > Parameters > Time synchronization > Synchroni-
zation interval
.
2.
Enter synchronization interval.
3.
Press the
Accept
button to save the modified parameter.
Reference time
You can use this parameter to set the reference time for time synchroniza-
tion that the device is to adopt and display. The following options are avail-
able:
Option
Description
UTC
The set UTC time is applied
Local time
The local time of the device is applied
Table 37: Reference time
To set the reference time, proceed as follows:
1.
Go to
Settings > Parameters > Time synchronization > Reference
time
.
2.
Select the option you want.
3.
Press the
Accept
button to save the modified parameter.
6.23.3
6.23.4
6.23.5