6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
126
5163667/00 EN
TRAFOGUARD® ISM®
Figure 91: Relative aging rate
Insulating paper (only with IEC 60076-7 calculation method)
You can use this parameter to set whether the transformer is equipped with
thermally stabilized insulation paper or not. This parameter is used to calcu-
late the relative aging rate and is only relevant if you calculate the hot-spot
temperature in accordance with IEC 60076-7.
Transformer age
You can use this parameter to set the current age of the transformer in
years. This parameter is used to calculate the aging rate.
Anticipated service life
You can use this parameter to set the anticipated service life of the trans-
former in years. This parameter is used to calculate the aging rate.
To set the parameters for calculating the aging rate, proceed as follows:
1.
Go to
Settings > Parameters > Rel. aging rate
.
2.
Select the parameter you want.
3.
Set the parameter you want.
4.
Press the Accept button to save the modified parameter.
Cooling system control (optional)
You can use the cooling system control function package to control and/or
monitor up to 6 cooling stages depending on device configuration. You can
set parameters for the following cooling stages:
Cooling stage
Meaning
S0
Operation without cooling stage
S1
Operation with cooling stage 1