3 Product description
Maschinenfabrik Reinhausen GmbH 2016
19
5163667/00 EN
TRAFOGUARD® ISM®
Performance features
Depending on your order, the device is equipped with the following optional
function packages:
▪
Basic monitoring
–
Voltage, current, frequency
–
Active power, reactive power, apparent power, power factor
–
Temperature monitoring (ambient temperature, temperature of top-
oil, temperature of bottom oil (optional), calculation of hot-spot tem-
perature in accordance with IEC 60076-7 or IEEE C57.91)
–
Optional: Transformer oil level
–
Loss-of-life and relative aging rate
–
Status of the motor-drive unit (motor protective switch, motor is run-
ning)
–
Tap position display
–
Optional: Status of protective devices (Buchholz relay, protective re-
lay, pressure relief device)
▪
On-load tap-changer monitoring
–
Contact wear calculation (only for OILTAP® V, M, R, RM, MS, G)
–
Maintenance interval calculation
–
Oil carbonization (only for OILTAP® V, M, R)
–
Monitoring of OLTC temperature (optional)
–
Tap-change statistics of on-load tap-changer
–
Optional: on-load tap-changer oil level
–
Optional: oil filter unit
–
Status of the motor-drive unit (motor protective switch, motor is run-
ning)
▪
Automatic voltage regulation AVR basic
–
Measurement of voltage and current
–
1 desired value
–
Voltage regulation with linear delay time T1
–
Status of the motor-drive unit (motor protective switch, motor is run-
ning)
▪
Automatic voltage regulation AVR pro
–
Measurement of voltage and current
–
Desired value in accordance with order (1, 3 or 5 desired values,
TDSC, analog desired value specification, gradual desired value
specification, desired value using BCD)
–
Automatic voltage regulation with linear or integral delay time T1
and with delay time T2
–
Parallel operation
–
Line drop compensation
3.3