6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
123
5163667/00 EN
TRAFOGUARD® ISM®
Displaying transformer statistics
To display the transformer statistics, proceed as follows:
► Go to
Information > Statistics
.
Figure 89: Transformer statistics
DGA monitoring
For the DGA monitoring "DGA", you can set 2 limit values each for moisture
content and gas content of the oil. The measured values are recorded via
the AIO assembly. You need to configure [
139] this assembly for this pur-
pose. You can display the current measured values by going to "Information"
under "DGA" [
Depending on the device configuration, you can monitor up to 11 DGA sig-
nals:
Gas
Parameter
Unit
H2O
H2O>
H2O>>
%
H2
H2>
H2>>
ppm
N2
N2>
N2>>
ppm
CO
CO>
CO>>
ppm
CO2
CO2>
CO2>>
ppm
CH4
CH4>
CH4>>
ppm
C2H2
C2H2>
C2H2>>
ppm
C2H4
C2H4>
C2H4>>
ppm
C2H6
C2H6>
C2H6>>
ppm
O2
O2>
O2>>
ppm
TDCG
TDCG>
TDCG>>
ppm
Table 31: Possible choice of gases
6.7.7
Содержание TRAFOGUARD ISM
Страница 1: ...Monitoring System TRAFOGUARD ISM Operating Instructions 5163667 00 EN ...
Страница 222: ......
Страница 223: ......