6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
102
5163667/00 EN
TRAFOGUARD® ISM®
Circuit G
▪
Three-phase measurement.
▪
The voltage transformers are connected between the phases.
▪
The current lags behind voltage by 30°.
If you use this circuit, set the device as follows:
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-
Phase angle correction
-
UI measuring channels
3-phase measurement (channels 1,
2, 3)
Measurement mode
Phase-phase
Table 20: Circuit G
Circuit H
▪
Three-phase measurement.
▪
The voltage transformers are connected between the phase and neutral
conductor.
Parameter
Option
Voltage-transformer circuit
-
Current-transformer circuit
-