6 Functions and settings
Maschinenfabrik Reinhausen GmbH 2016
188
5163667/00 EN
TRAFOGUARD® ISM®
Linking digital outputs
When you link a digital output to an event, the device issues a signal to that
output if the event occurs. The signal persists until the event stops. A param-
eter is available for each available digital output.
Figure 135: Linking digital outputs
In order to establish the link, you have to enter the corresponding event
number at the desired parameter.
If you enter event number 500, the link is deactivated.
To link the digital output, proceed as follows:
ü
The desired event number is known.
1.
Go to
Settings > Parameters > Link digital outputs
.
2.
Select the parameter you want.
3.
Enter the desired event number.
4.
Press the
Accept
button to save the modified parameter.