Setup
Chapter Four: Local Operation
44
Settings stored in non-volatile RAM are saved when the power is turned
off. When the power is restored, the 651 unit “remembers” the latest
configuration, not the initial configuration.
To enter the Setup Menu to configure the operating parameters:
1. Press the [
] and [
] keys simultaneously for about three seconds.
The screen displays:
CONTROL
MODE PID
Select the desired pressure control mode, PID.
2. Press the [
] key to advance to the next screen.
The screen displays:
BAUD RATE: 9600
Select the baud rate from the options of 300, 1200, 2400, 4800, 9600 (initial), and 19200.
3. Press the [
] key to advance to the next screen.
The screen displays:
PARITY: NONE
Select the parity from the options of NONE (no parity / 8 data bits - initial) or EVEN
(even parity / 7 data bits).
Содержание 651D Series
Страница 1: ...118965 P1 Preliminary 5 02 MKS Type 651D Pressure Controller...
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 20: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Страница 50: ...Labels Chapter Three Overview 38 This page intentionally left blank...
Страница 78: ......
Страница 107: ...Chapter Five Remote RS 232 Operation Setup Messages 95 To change the softstart rate for set point A to 50 enter I 1 50...
Страница 130: ...How To Activate the Softstart Rate Chapter Six Remote Digital Logic Control 118 This page intentionally left blank...
Страница 142: ...Troubleshooting Chapter Seven Maintenance and Troubleshooting 130 This page intentionally left blank...
Страница 149: ...Appendix C Initial Settings 137 This page intentionally left blank...
Страница 150: ......
Страница 158: ...Appendix E RS 232 Message Summary 146 This page intentionally left blank...