Chapter Two: Installation
Connectors
21
Interface (I/O) Connector
The 37-pin female Type “D” Interface (I/O) connector provides access to the set points, process
relay limits, softstart control, and the valve control functions.
Interface Connector Pinout
Pin Number
Assignment
Pin Number
Assignment
1
PLO 1 - NC contact
20
PLO 1 - common contact
2
PLO 1 - NO contact
21
PLO 2 - common contact
3
PLO 2 - NC contact
22
PLO 2 - NO contact
4
Digital ground
23
Valve closed status (hi = closed)
5
Reserved
24
Learn Valve (low)
6
Analog set point
position
control
Hold
both
pins 6 and 11 low.
25
Remote zero (low)
7
Softstart (low)
26
Stop valve (low)
8
Close valve (low)
27
Open valve (low)
9
Analog input channel select
hi = Channel 1; low = Channel 2
28
(output) PLO 2 status
(low = out of limit)
10
Analog set point ÷ 10
29
(output) PLO 1 status
(low = out of limit)
11
Analog set point control
Hold
only
pin 11 low to select
pressure control.
Hold
both
pins 6 and 11 low to
select position control
30
+15 V Output
12
Select set point E (low)
31
-15 V Output
13
Select set point D (low)
32
Power ground
14
Select set point C (low)
33
+ Set point input
15
Select set point B (low)
34
- Set point input*
16
Select set point A (low)
35
Analog ground*
17
Zeroed pressure output voltage
for low range transducer
(Channel 2)
36
Zeroed pressure output voltage
for high range transducer
(Channel 1)
18
Reserved
37
Position output voltage
19
Valve open status (hi = open)
* The analog set point must be referenced to analog ground. If you are using an absolute
Содержание 651D Series
Страница 1: ...118965 P1 Preliminary 5 02 MKS Type 651D Pressure Controller...
Страница 8: ......
Страница 10: ......
Страница 12: ......
Страница 20: ...Customer Support Chapter One General Information 8 This page intentionally left blank...
Страница 50: ...Labels Chapter Three Overview 38 This page intentionally left blank...
Страница 78: ......
Страница 107: ...Chapter Five Remote RS 232 Operation Setup Messages 95 To change the softstart rate for set point A to 50 enter I 1 50...
Страница 130: ...How To Activate the Softstart Rate Chapter Six Remote Digital Logic Control 118 This page intentionally left blank...
Страница 142: ...Troubleshooting Chapter Seven Maintenance and Troubleshooting 130 This page intentionally left blank...
Страница 149: ...Appendix C Initial Settings 137 This page intentionally left blank...
Страница 150: ......
Страница 158: ...Appendix E RS 232 Message Summary 146 This page intentionally left blank...