268
-
'16 • SCM-T-199
Error code
Remote control:
LED
Green
Red
Indoor Keeps flashing Stays OFF
Content
E47
Active filter voltage error
Outdoor
–
2
-
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
YES
YES
NO
Is the power source normal?
NO
Check
soldered surfaces on the
outdoor sub PCB for foreign matter
like dust, fouling,
etc.
YES
Is voltage
within the specified range?
NO
Restore normal condition.
Restore normal condition.
Remove foreign matter like
dust, fouling, etc.
Defective outdoor sub PCB
→
Replace.
2. Error detection method
Error is displayed if the
converter voltage exceeds
DC340V (3 times within 20
minutes). Remote control may
be set after 3 minutes delay.
3. Condition of error displayed
Same as above
4. Presumable cause
• Defective outdoor sub PCB
• Dust on outdoor sub PCB
• Anomalous power source
Note: