230
-
'16 • SCM-T-199
[Operating procedure]
(i) On the TOP screen, touch the buttons in the order of “Menu”
→
“Next”
→
“Service & Maintenance”
→
“Service
password”
→
“Set”
→
“Error display”
→
“Error history”.
(ii) When only one indoor unit is connected to the remote control, followings will be displayed.
1. When there is any anomaly: “Loading. Wait a while” is displayed, followed by the operation data at the occurrence of
anomaly. Contents of display
・
Error code
・
Number and data item
2. When there is no anomaly: “No anomaly” is displayed, and this mode is terminated.
(iii) When two or more indoor units are connected to the remote control, followings will be displayed.
1. When there is any anomaly: If the unit having anomaly is selected on the “Select IU” screen, “Loading. Wait a while” is
displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・
Indoor unit No.
・
Error code
・
Number and data item
2. When there is no anomaly: “No anomaly” is displayed, ant this mode is terminated.
Note (1) When the number of connected units cannot be shown in a page, select “Next”.
(iv) If you press [RUN/STOP] button, the display returns to the TOP screen.
◎
If you touch “Back” button on the way of setting, the display returns to the last precious screen.
Note (1) When two remote controls are used to control indoor units, the check of anomaly operation data can be made on the master remote control only. (It
cannot be operated from the slave remote control.)
■
Anomaly operation data (Corresponding data may not be provided depending on models. Such items will not be displayed.)
Number
01
02
03
04
05
06
07
08
09
10
11
12
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
Data Item
(Operation Mode)
(Set Temperature)
(Return Air Temperature)
(Remote Control Thermistor Tempeature)
(Indoor Heat Exchanger Thermistor / U Bend)
(Indoor Heat Exchanger Thermistor /Capillary)
(Indoor Heat Exchanger Thermistor /Gas Header)
(Indoor Unit Fan Speed)
(Frequency Requirements)
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
(Total Running Hours of The Indoor Unit)
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Thermistor)
(Outdoor Heat Exchanger Thermistor)
(Compressor Frequency)
(High Pressure)
(Low Pressure)
(Discharge Pipe Temperature)
(Comp Bottom Temperature)
(Current)
(Target Super Heat)
(Super Heat)
(Discharge Pipe Super Heat)
(Protection State No. of The Compressor)
(Outdoor Unit Fan Speed)
(63H1 On/Off)
(Defrost Control On/Off)
(Total Running Hours of The Compressor)
(Pulse of The Outdoor Unit Expansion Valve EEVC)
(Pulse of The Outdoor Unit Expansion Valve EEVH)
(b) In case of RC-EX1A remote control
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...