'16 • SCM-T-199
None
Power source system error
(Power source to indoor control PCB)
Stays OFF Stays OFF
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
AC220/240V
detected between
①
and
②
on the terminal block
of indoor
unit?
NO
NO
Are fuses
OK (F200, F201)?
YES
YES
NO
Is the
check of resistance between
①
-
③
of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
Is
AC220/240V
for 1-phase unit detected between
①
and
②
on the terminal
block of outdoor
unit?
YES
YES
NO
(2)
(1)
Note (2)
⑤
for GND
Note (1) FDE, FDUM:F1, F2
Is DC5V detected
between
④
-
⑤
of CNW1
(FDTC:CNW2)?
NO
YES
YES
Is JX1 open?
YES
Defective outdoor sub PCB
(Noise filter)
Misconnection or breakage
of connecting wires
Defective indoor control or
power PCB
→
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor power
PCB
→
Replace.
Open JX1.
Defective indoor control
PCB
→
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor sub PCB
(Noise filter)
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...