254
-
'16 • SCM-T-199
E11
Address setting error of
indoor units
Keeps flashing Keeps flashing
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
• In cases of RC-EX1A
Menu
→
Next
→
IU settings
→
Select IU
• In cases of RC-E5
Return address No. to
“IU …” using [
▲
] or
[
▲
] button.
2. Error detection method
IU address has been set using
the “Master IU address set”
function of remote control.
3. Condition of error displayed
Same as above
4. Presumable cause
Same as above
Note:
Is “Master IU
address set” function of remote
control used?
E11 occurs
YES
IU
IU
IU
R/C
In case the wiring is below and “Master IU address
set” is used, E11 is appeared.
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SCM40ZS-S