'16 • SCM-T-199
E7
Return air temperature
thermistor anomaly
Keeps flashing 1-time flash
Outdoor
–
Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
NO
YES
Is the
connection of return
air temperature thermistor
connector OK?
Are the
characteristics of return air
temperature thermistor
OK?
YES
15
10
5
0
10
30
40
20
50
Temperature-resistance characteristic
Te
mperature thermistor resistance (k
Ω
)
Temperature (°C)
5k
Ω
at 25
°C
(Broken wire)
(Short circuit)
Correct.
→
Connect
connector.
Defective return air
temperature thermistor
→
Replace.
Defective indoor control
PCB
→
Replace.
(Defective return air
temperature thermistor
input circuit)
2. Error detection method
Anomalously low temperature
or high temperature (resistance)
is detected by indoor return air
temperature thermistor (Thi-A)
3. Condition of error displayed
• When the temperature thermistor
detects -50°C or lower for
5 seconds continuously, the
compressor stops. After 3-minute
delay, the compressor starts again
automatically, but if this error
occurs again within 60 minutes
after the initial detection.
4. Presumable cause
• Defective return air
temperature thermistor
connector
• Defective return air
temperature thermistor
• Faulty indoor control PCB
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...