262
-
'16 • SCM-T-199
E37
Outdoor heat exchanger
temperature sensor anomaly
Keeps flashing
Stays OFF
Outdoor
–
8
-
time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
outdoor heat
exchanger temperature
sensor connector
connected
properly?
YES
Are the
characteristics of
outdoor heat exchanger
temperature
sensor
OK?
NO
For the characteristics of outdoor heat exchanger
temperature sensor, see the following graph.
YES
Temperature-resistance characteristics
Temperature sensor resistance (k
Ω
)
Temperature (°C)
15
10
5
0
10
30
40
20
50
5k
Ω
at 25°C
NO
(Broken wire)
(Short circuit)
Correct connector.
Defective outdoor heat
exchanger temperature
sensor
→
Replace.
Defective outdoor main
PCB
→
Replace.
(Defective outdoor heat
exchanger temperature
sensor input circuit)
2. Error detection method
Detection of anomalously low
temperature (resistance) on
the outdoor heat exchanger
temperature sensor
3. Condition of error displayed
• When the temperature sensor
detects -55 °C or lower for 20
seconds continuously within
2 minutes to 2 minutes 20
seconds after the compressor
ON, the compressor stops.
After 3-minutes delay, the
compressor starts again
automatically, but if this
anomalous temperature is
detected 3 times within 40
minutes.
• When -55 °C or lower is
detected for within 20 second
after power ON.
4. Presumable cause
• Defective outdoor main PCB
• Broken sensor harness or
temperature sensing section
• Disconnected wire connection
(connector)
Note:
Error code
Remote control:
LED
Green
Red
Indoor
Content
Содержание SCM40ZS-S
Страница 114: ...113 16 SCM T 199 source PJA012D783...
Страница 200: ...199 16 SCM T 199 4 Troubleshooting procedure If the air conditioner runs NO NO NO NO YES YES YES YES 200 201 207 201 207...
Страница 285: ...284 16 SCM T 199 B PJZ012D077 2 Model RC EX1A eco touch REMOTE CONTROL RC EX1A INSTALLATION MANUAL...
Страница 311: ...310 16 SCM T 199 4 10 5 Superlink E board SC ADNA E F SL2NA E and SL4 AE BE to control...
Страница 312: ...311 16 SCM T 199...